• sns041
  • sns021
  • sns031

GPN1-40.5kV Amovibilibus AC Metallicis Clauditur Switchgear

Description:

GPN1-40.5kV amovibiles AC metallo-lastros switchgear (brevis pro switchgear ut infra) valet pro 40.5kV, 3 phase, AC et 50/60Hz electrica vim retis recipiendi et distribuendi vim energiam ac etiam ad imperium, monitorem et tutelam.


Product Detail

Product Tags

Summarium

GPN1-40.5kV amovibiles AC metallo-lastros switchgear (brevis pro switchgear ut infra) valet pro 40.5kV, 3 phase, AC et 50/60Hz electrica vim retis recipiendi et distribuendi vim energiam ac etiam ad imperium, monitorem et tutelam.Adhibetur in generali potentia ratio et occasiones cum frequenti operatione.Productum conforme GB 3906 "3~35kV AC Metallum Inclusum Switchgear", GB/T 11022 "Communes technicae clausulae altae intentionis Switchgear ac controlgear Standard", DL/T 404-1997 "Ordo technicae terminorum Indoor AC High Voltage Switchgear "et IEC-298 "1~52kV AC Metallum Inclusum Switchgear et vexillum Controlgear".

Ambiens Condition

Temperatura ambiens: -25℃~+45℃, mediocris cotidie: ≤35℃
Altitude: 1000m (Latin);potest ad 4500m pro speciali ordinatione;
Relativum humiditas: cotidie mediocris ≤ XCV%, menstrua mediocris ≤ XC%;
Terrae motus intensio≤8 est gradus;
Occasiones utilia esse debent ab erodentibus, inflammabilibus, et vaporibus.

Model

img1

Product Feature

Switchgear unitas conventus est et praevaricator ambitus exemplar tabulati carri adoptat.Possidet simpliciter mutationem et bene permutationem instruendi cum progressu composito velit vacui circuli ruptor.Cochleae plumbeae propulsionis mechanismi nucis instituitur in car- marum ad impediendum a culpa operante et damnosa propulsio mechanismo, carrum facile removeri potest;Omnes operationis gradus in clausula conditione perfici possunt;Coactum est obstruere inter transitum principalem, carrum et ostiolum ad quinque praesidia occurrere;latum spatium ad plures rudentes in cubicle connectendi.Transitus terrestris in circumscriptione terrestri et ansa brevi adhibetur, gradus custodiae clausurae IP3X, IP2X sub conditione aperitur.

Technical Specification

Nec.

Item

Unitas

Data

1

Rated voltage

kV

36/38/40.5

2

Ratum current

A

1250, 1600, 2000, 2500

3

Rated frequency

Hz

50/60

4

Ratum brevis circuitio praevaricationis current

kA

XXV, 31.5

5

4s sustinere brevi tempore current rated

kA

XXV, 31.5

6

Aestimavit ambitum brevem currentem faciens (apicem)

kA

63, 80

7

Rated apicem sustinere current (cacumen)

kA

63, 80

8

Nulla gradu

Rated fulgura impetus sustinere voltage

kV

185 (per contactum apertum: 215).

Pelagus circa 1min potentia frequentia resistunt intentione

kV

95 (per contactum apertum: 110);

Circuitus auxiliaris 1min potentiae frequentiae intentioni resistunt

kV

2

9

Divisio dimensionis (W) * (D) * (H)

mm

1400/2800/2600 (GPN1 type)

1200/2600/2400 (type VD4/HD4)

10

Praesidium gradum

 

IP3X (compartment IP2X)

11

Pondus

kg

1000-1850 (GPN1 type)

850-1850 (Pro type VD4/HD4)

Structura Feature

Switchgear in clausuram et carrum dividit, clausura facta est schedae aluminii-zinci patellae ferri, postquam processit machinae CNC et multi-flexae, deinde clausurae coactae sunt.Ita validas mechanicas vires habet et concinnitatem et speciem bonam praestare potest.Constat e nulla cellula, carro camera, cable compartamento, gradus tutelae IP2X est cum carrum CB in apertione et positione probatio est.

Switchgear genus metallicum amovibilibus, ambitus principalis, processus insulationem compositam capit, in alias partes subitis dilatans.CT et commutatio terrestris in cable compartment et busbar concamerantur.Gradus custodiae clausurae est IP3X, tutela et spatium magnum aliquot funibus.Consilium fabricae novae omnino insulatae VCB vel SF6 CB et fons mechanismus operans integratur exemplar consolatorium cum tali excellentia bene commutationis et mutationis simpliciter.

Forma ratio Switchgear

img2
img3

  • Previous:
  • Deinde:

  • Related Products

    >