GPR-24(12)kV Series Ring Main Unit Switchgear
Summarium
GPR-24 series Ring Main Unit est extensibilis, SF6 insulata switchgear, cum voltage 12&24 kV aestimata.Omnes eius HV partes vivae in cisternina gasi-arte continentur, quae ex ferro immaculato 3mm conficitur.Tota conventus mutandi SF6 insulata est, et ab omni externa influentia libera, magna cum fiducia servitii et sustentationis libera.Per obturaculum-in speciebus extensionis busbaricae, GPR-24 series Ring Main Unit potest esse liberae complexionis et modularisationis plena.Busbar extensio genus experimentum potentiae et stabilitatis scelerisque transiit, et plene insulata et tuta est, altam fidem et salutem exhibens.GPR-24 series Ring Main unitas apta est omnibus MV network usque ad 24 kV, omnes stationes potentiae compactae, potestas distributio substations in omnibus industriis magni momenti, ut industria petrol-chemica, metallurgica et fodienda industriae, et omnes transformator substations et potentiae venti. ratio.
Features
1. Provectus ars ad Gas cisternina
Systema laseris digitalis continentis incisionis et pulsationis ac trium dimensionis et systematis laseris quinque-axis glutino ex Germania importato, cum emissiones gasorum et uniformitas omnium praediorum gasorum curet.
Systema deprehensionis plene latis et integrale helium effluo, factum a SEILER Vakuumtechnik GmbH, detectum lacus helium per spectrographum massa, ratem gasi lacus per annum usque ad minus quam 0.02% affert, ut vitae spatium gasi supra 30 annorum.
Processus processus artis pro partibus .
Omnes epoxy resinae resinae insulatae, incluso polo insulatae, fabricantur per epoxy resinam plene automaticam et digitally moderatam vacui mixtionis / pressuris systematis gelatinizationis ab Hedrich (Germania) .
Busbar connectoris, funis connectoris, finis obturaculum et aliae silicones globulus partium insulatarum fabricatur a plene automatico et digitally regente silicone globulus mixtionis/pressionis systematis gelatinizationis ab VOGEL(Helvetiae).
2. Optima solutiones pro products
Cum structura parva et compacta, unitates fundamentales functiones K, T, V, B et C aequabiles habent dimensiones: 350*800*1380 mm (latitudinis altitudo).
Solutiones integrae:
Unius versio una: onus interrumpendum transitum unitatis, unitas switch-fuse, vacuus ambitus ruptor unitatis, ordo busbarum unitas, funis unitas, metering unitas, etc.
Obstructionum versio effici potest ex duabus, tribus, quattuor, quinque vel sex unitates functionis.
Singulae unitates et versionem scandalum molliter connecti possunt per connexiones busbaricae.
Fortis apta 3. ad environment
Prima ratio conductiva in piscina SF6 gasi plene obsignata et ab extra ambitum non commovetur, sine impulsu roris, pulveris, salis nebulae, etc. .
12kV Technical Data
Descriptio | Unitas | LBS unitas | Fuse unitas switch- | VCB unitas | Busbar ordo unitatis | |
Rated voltage | kV | 12 | 12 | 12 | 12 | |
Potestas frequentiae sustinere intentionem (1min) | Tempus ad tempus / terra | kV | 42 | 42 | 42 | 42 |
Per solitudinem spatium | kV | 48 | 48 | 48 | 48 | |
Impetus sustinere voltage | Tempus ad tempus / terra | kV | 75, (95)*. | 75, (95)*. | 75, (95)*. | 75, (95)*. |
Per solitudinem spatium | kV | 85, (110)*. | 85, (110)*. | 85, (110)*. | 85, (110)*. | |
Rated frequency | Hz | 50,60 | 50,60 | 50,60 | 50,60 | |
Ratum current | A | 630 | 630 | 630 | ||
Ratum brevis circuitio praevaricationis current | kA |
| 20,(25)* |
| ||
Rated breve tempus sustinere current | KA/s | 20/3; (20/4, 25/1)*. |
| 20/3; (20/4, 25/3)*. | 20/3; (20/4, 25/1)*. | |
Rated apicem sustinere current | kA | 50, (63)*. |
| 50, (63)*. | 50, (63)*. | |
Ratum ambitum brevem currentem faciens | kA | 50, (63)*. | 50, (63)*. | 50, (63)*. | ||
Ratum translatio current | A |
| 1800 |
|
| |
Rated activae onus fractionis current | A | 630 |
|
| 630 | |
Rated clausa loop fractionis current | A | 630 |
|
| 630 | |
V% rated activae onus fractionis current | A | 31.5 |
|
| 31.5 | |
Rated operating seriem |
|
|
| O-0.3s-CO-180s-CO |
| |
Mechanica vita | Ad Opem. | 5000 | 5000 | 10000 | 5000 | |
Vita electrica |
| E3 |
| E2 | E3 | |
Crassitudo immaculata ferro | mm | 3.0 | ||||
Ratum SF6pressura | kPa | 30 (ad 20℃, 101.3kPa) | ||||
Annua rate lacus | <0.02% | |||||
Aqua curatio test | 12kV XXIV horas (ante XXX kPa sub aqua) | |||||
Arcus internus test | 20kA 1s | |||||
Praesidium gradum | Gas tank | IP 67 | ||||
Fuse possessor | IP 67 | |||||
GPR clausura |
| IP 4X |
24kV Technical Data
Descriptio | Unitas | LBS unitas | Fuse unitas switch- | VCB unitas | Busbar ordo unitatis | |
Rated voltage | kV | 24 | 24 | 24 | 24 | |
Potestas frequentiae sustinere intentionem (1min) | Tempus ad tempus / terra | kV | 50, (65)*. | 50, (65)*. | 50, (65)*. | 50, (65)*. |
Per solitudinem spatium | kV | 64, (79)*. | 64, (79)*. | 64, (79)*. | 64, (79)*. | |
Impetus sustinere voltage | Tempus ad tempus / terra | kV | 95, (125)*. | 95, (125)*. | 95, (125)*. | 95, (125)*. |
Per solitudinem spatium | kV | 110, (145)* | 110, (145)* | 110, (145)* | 110, (145)* | |
Rated frequency | Hz | 50, 60 | 50, 60 | 50, 60 | 50, 60 | |
Ratum current | A | 630 | 630 | 630 | ||
Ratum brevis circuitio praevaricationis current | kA |
| 20 |
| ||
Rated breve tempus sustinere current | KA/s | 20/3, (20/4)* |
| 20/3, (20/4)* | 20/3, (20/4)* | |
Rated apicem sustinere current | kA | 50 |
| 50 | 50 | |
Ratum ambitum brevem currentem faciens | kA | 50 | 50 | 50 | ||
Ratum translatio current | A |
| 1400 |
|
| |
Rated activae onus fractionis current | A | 630 |
|
| 630 | |
Rated clausa loop fractionis current | A | 630 |
|
| 630 | |
V% rated activae onus fractionis current | A | 31.5 |
|
| 31.5 | |
Rated operating seriem |
|
|
| O-0.3s-CO-180s-CO |
| |
Mechanica vita | Ad Opem. | 5000 | 5000 | 10000 | 5000 | |
Vita electrica |
| E3 |
| E2 | E3 | |
Crassitudo immaculata ferro | mm | 3.0 | ||||
Rated SF6 pressura | kPa | 30 (ad 20℃, 101.3kPa) | ||||
Annua rate lacus | <0.02% | |||||
Aqua curatio test | 24kV XXIV horas (ante XXX kPa sub aqua) | |||||
Arcus internus test | 20kA 1s | |||||
Praesidium gradum | Gas tank | IP 67 | ||||
Fuse possessor | IP 67 | |||||
GPR clausura | IP 4X |
Notae:
① Rated current of switch-fuse unitatis dependet ex aestimatione fuse: ≤100A
② Rated brevis circuit fractionis/faciens current of switch unitas pendent ex aestimatione fuse
* Valores in uncis speciales requisita sunt, pete fabricatorem vel elit pro magis informatione
GPR24 Series Overview
1. Una tristique genus
Nota:
1. Pretio uncis notata cum "*" producta sunt ad 24kV, potentia frequentiae intentioni 65/79kV resistendi;
2. Si plura in schemate parte secundaria insunt, adiectio eorum in super tabula collocari potest, altitudo eius 400 mm est.
2. GPR24 Clausus type-1 pro 12kV & 24kV (potentiam frequentiam sustinent intentione: 50/64kV)
Notae:
Si nimis multa secundaria in schemate dentur, eis addita cellula constitui potest super GPR, eius altitudo 400mm est.